CVE-2026-9128: Rockwellautomation Studio 5000 Logix Designer

High severity, CVSS 7.5. EPSS: 0.2% chance of exploitation in the next 30 days.

A code execution security issue exists within Studio 5000 Logix Designer® due to an unquoted search path in the External Tools configuration. The executable paths specified in the external tools configuration file are not properly quoted, and because these paths contain spaces, the operating system may resolve them to unintended executables placed earlier in the search order. If exploited, an attacker could plant a malicious executable in a location within the search path, resulting in arbitrary code execution with the same permissions of the user running the application.

Affected products

  • Rockwellautomation Studio 5000 Logix Designer: before 32.05 (fixed in 32.05); from 33.00, before 33.03 (fixed in 33.03); from 34.00, before 34.03 (fixed in 34.03); version 35.00 only

Published 2026-07-14. Last modified 2026-08-25.