CVE-2026-25787: Siemens SIMATIC Drive Controller CPU 1504d Tf

Critical severity, CVSS 9.1. EPSS: 0.5% probability of exploitation activity in the next 30 days.

Affected devices do not properly validate and sanitize Technology Object (TO) name rendered on the "Motion Control Diagnostics" page of the web interface. This could allow an authenticated attacker who is authorized to download a TIA project into the product, to inject malicious scripts into the page. If a benign user with appropriate rights accesses the "Motion Control Diagnostics" parameters page, the malicious code would be executed in the scope of their web session.

What to do

The record states a fixed version for each range of affected versions. Update to the one for the range your version is in: a later release on another branch may not have the fix.

  • Siemens SIMATIC Drive Controller CPU 1504d Tf, before V3.1.6: fixed in V3.1.6
  • Siemens SIMATIC Drive Controller CPU 1507d Tf, before V3.1.6: fixed in V3.1.6
  • Siemens SIMATIC Et 200sp CPU 1510sp-1 Pn, before V2.9.9: fixed in V2.9.9
  • Siemens SIMATIC Et 200sp CPU 1510sp-1 Pn, before V4.1.6: fixed in V4.1.6
  • Siemens SIMATIC Et 200sp CPU 1510sp F-1 Pn, before V2.9.9: fixed in V2.9.9
  • Siemens SIMATIC Et 200sp CPU 1510sp F-1 Pn, before V4.1.6: fixed in V4.1.6
  • Siemens SIMATIC Et 200sp CPU 1512sp-1 Pn, before V2.9.9: fixed in V2.9.9
  • Siemens SIMATIC Et 200sp CPU 1512sp-1 Pn, before V4.1.6: fixed in V4.1.6
  • Siemens SIMATIC Et 200sp CPU 1512sp F-1 Pn, before V2.9.9: fixed in V2.9.9
  • Siemens SIMATIC Et 200sp CPU 1512sp F-1 Pn, before V4.1.6: fixed in V4.1.6
  • and 87 more

Affected products

Published 2026-05-12. Last modified 2026-07-14.