CVE-2020-7540: Schneider Electric 140cpu65150 Firmware

Critical severity, CVSS 9.8. EPSS: 2.3% probability of exploitation activity in the next 30 days.

A CWE-306: Missing Authentication for Critical Function vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause unauthenticated command execution in the controller when sending special HTTP requests.

What to do

The record states a fixed version for each range of affected versions. Update to the one for the range your version is in: a later release on another branch may not have the fix.

  • Schneider Electric 140cpu65150 Firmware, before 6.1: fixed in 6.1
  • Schneider Electric 140cpu65160 Firmware, before 6.1: fixed in 6.1
  • Schneider Electric 140noc77101 Firmware, before 1.08: fixed in 1.08
  • Schneider Electric 140noc78000 Firmware, before 1.74: fixed in 1.74
  • Schneider Electric 140noc78100 Firmware, before 1.74: fixed in 1.74
  • Schneider Electric 140noe77101 Firmware, before 7.1: fixed in 7.1
  • Schneider Electric 140noe77111 Firmware, before 7.1: fixed in 7.1
  • Schneider Electric BMXNOC0401 Firmware, before 2.10: fixed in 2.10
  • Schneider Electric BMXNOE0100 Firmware, before 3.3: fixed in 3.3
  • Schneider Electric BMXNOE0110 Firmware, before 6.5: fixed in 6.5
  • and 12 more

Affected products

Published 2020-12-11. Last modified 2026-06-17.