CVE-2020-5802: Rockwellautomation Factorytalk Linx
High severity, CVSS 7.5. EPSS: 45% probability of exploitation activity in the next 30 days.
An attacker-controlled memory allocation size can be passed to the C++ new operator in RnaDaSvr.dll by sending a specially crafted ConfigureItems message to TCP port 4241. This will cause an unhandled exception, resulting in termination of RSLinxNG.exe. Observed in FactoryTalk 6.11. All versions of FactoryTalk Linx are affected.
What to do
No fixed version is stated in NVD's or the CNA's structured data. Check the vendor's advisory among the references.
Affected products
- Rockwellautomation Factorytalk Linx: up to and including 6.11
Published 2020-12-29. Last modified 2026-06-17.