CVE-2020-27736: Siemens Nucleus Net

Medium severity, CVSS 6.5. EPSS: 3.6% chance of exploitation in the next 30 days.

A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected DNS modules), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS domain name label parsing functionality does not properly validate the null-terminated name in DNS-responses. The parsing of malformed responses could result in a read past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition or leak the read memory.

Affected products

  • Siemens Nucleus Net: any version
  • Siemens Nucleus Readystart v3: before 2017.02.3 (fixed in 2017.02.3)
  • Siemens Nucleus Readystart v4: before 4.1.0 (fixed in 4.1.0)
  • Siemens Nucleus Source Code: affected versions not specified
  • Siemens Simotics Connect 400 Firmware: before 0.5.0.0 (fixed in 0.5.0.0)

Published 2021-04-22. Last modified 2026-06-17.