CVE-2019-6808: Schneider Electric Modicon m340 Firmware
Critical severity, CVSS 9.8. EPSS: 8.2% probability of exploitation activity in the next 30 days.
A CWE-284: Improper Access Control vulnerability exists in all versions of the Modicon M580, Modicon M340, Modicon Quantum, and Modicon Premium which could cause a remote code execution by overwriting configuration settings of the controller over Modbus.
What to do
The record states a fixed version for each range of affected versions. Update to the one for the range your version is in: a later release on another branch may not have the fix.
- Schneider Electric Modicon m340 Firmware, before 3.10: fixed in 3.10
- Schneider Electric Modicon m580 Firmware, before 2.90: fixed in 2.90
Affected products
- Schneider Electric Modicon m340 Firmware: before 3.10 (fixed in 3.10)
- Schneider Electric Modicon m580 Firmware: before 2.90 (fixed in 2.90)
- Schneider Electric Modicon Premium Firmware: up to and including 3.20
- Schneider Electric Modicon Quantum Firmware: up to and including 3.60
Published 2019-05-22. Last modified 2026-06-17.